Hot water coils are usually 1 or 2 rows and chilled water coils are usually 3 to 12 rows deep.
Chilled water cooling coil design.
Designated by the fluids in the tube.
Understand the balance of coil face area airside pressure drop and waterside pressure drop when selecting a coil 5.
So a chilled water coil is a fin and tube heat exchanger used for cooling air where the coolant is chilled water and the direct expansion coil is a fin and tube evaporator found in a vapour compression cycle.
Evaluate water coil selection choices at various water temperatures and flow rates 4.
The chilled water supply temperature usually has a fixed set point and the only variable that affects the output capacity of chiller is the return water temperature.
Chilled water coils are one of the most common mediums for cooling air.
For a given design load the chiller is selected for fixed temperature range t and the associated chilled water pumps are selected for calculated flow rate.
As warm air passes across the coil and comes in contact with the cold surface of the fins heat then transfers from the air to the water flowing through the tubes both cooling and dehumidifying the air.
Methods to design the cooling and dehumidifying coil either chilled water coil or dx evaporator coil are usually based on log mean enthalpy or log equivalent dry bulb temperature difference.
There is really no difference between hot water coils and a chilled water coils in construction.
The chilled water is generated and circulated in the primary side the secondary loops will pull chilled water out of the header to cool the building and then dump the warm return back into the header.
The vast majority of chilled water coils are constructed from either 1 2 od tubes or 5 8 od tubes.
Chilled water cooling coil selection example 4 chilled water coil worksheet example 5 chilled water coil worksheet 6 enthalpy of air table 1 7 air density correction at altitude table 2 7 air density correction at temperature table 3 7 log mean temperature difference table 4 8 basic capacity figure 1 8fpi 9 basic capacity figure 2 1ofpi 10.
Properly protect water coils from freezing when necessary agenda water and air velocity ranges coil selection examples chilled.
Beginning in its 2016 version ashrae standard 90 1 now requires chilled water cooling coils be designed for at least a 15 f temperature difference δt between the leaving and entering water.
And the leaving water temperature must be no colder than 57 f at design conditions 1.
In chilled water system design the low coil temperatures required for this process dictate the design chilled water temperature 42 44 f.